12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA) 12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA)

12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type (2U 3KVA)

Model:SPI-R2 series (2U 3KVA)

Type:
IGBT / PWM Type

Capacity:
3KVA (2U)

Made in:
Taiwan, ROC

Add in inquiry Download

• AC Power for Battery

• ATS

• Automation

• Car Electrification

• Civil and Military Nautical

• Emergency Lighting

• ETC

• Medical Equipment

• Railway Field

• Telecom System

Clean,Highly Regulated Power Supply !

• For Telecom:12 / 24 / 48Vdc DC Voltage.

• For Power Plant:110 / 220Vdc DC Voltage.

• 1U / 2U / 3U 19" or 23" Rack-mount type.

• 1U / 2U / 3U 19" or 23" Open Frame Cabinet.

• Digital Displays.

• Pure Sine Wave Output (THD <3%) Resistive Load.

Bypass Function.

• Advanced Microprocessor.

Inverter mode / UPS mode (Option)

• Built-in Transfer Switch.

• Loading & Temperature Controlled Cooling Fan.

• Output Frequency : 50 / 60Hz Switch.

• Adjustable Output Voltage.

• Reliable Input Surge Protection & EMI Suppression.

• Modularized IGBT infrastructure to ensure better durability.

• Cold start function (DC start) functionality allows unit to operate with battery only.

• RS-232 Interface / Wire Connection to PC.

• Option: SNMP Interface / Dry Contacts / Remote Control.

• Protection : Input Under Voltage, Input Over Voltage, Overload, Short Circuit,

Low Battery Alarm, Over Temperature.

CUSTOMIZATIONS WELCOME

2U 19" Rack Mount Type (3KVA)

Model

A:110V

E: 220V

SPI-R2-

1203A

SPI-R2-

2403A

SPI-R2-

4803A

SPI-R2-

1103A

SPI-R2-

2203A

SPI-R2-

1203E

SPI-R2-

2403E

SPI-R2-

4803E

SPI-R2-

1103E

SPI-R2-

2203E

Outlook Rack Mount  19" 2U
Capacity Continuous O/P Power 3000W
Surge Rating 3200W @ 3 Minutes
3500W @ 3 Seconds
Peak 6000W
DC Input  I/P Voltage (Vdc)  12  24 48 110
220
12 24 48 110 220
I/P Voltage Range (Vdc) 10-16 20-32 42-62 90-140
180-275
10-16 20-32 42-62 90-140 180-275
Over Voltage Alarm (Vdc) 15.5 31.0 61.0 135.0 270.0 15.5 31.0 61.0 135.0 270.0
Over Voltage Cut-off (Vdc) 16.0 32.0 62.0 140.0 275.0
16.0 32.0 62.0 140.0 275.0
Under Voltage Alarm (Vdc) 10.5 21.0 43.0  95.0 185.0
10.5 21.0 43.0 95.0 185.0
Under Voltage Cut-off (Vdc) 10.0 20.0 42.0  90.0 180.0
 10.0 20.0 42.0 90.0 180.0

Bypass

(AC Input)

Nominal Voltage     A: 1 Phase 2W+G, 110Vac (90V - 130Vac)      E: 1 Phase 2W+G, 220Vac (180V - 260Vac)
Frequency (50Hz - 60Hz) ± 3%      (50Hz / 60Hz) ± 3%
Protection Electronic Circuits & AC Circuit Breaker
Bypass Inverter ⇔ Bypass 4 - 6 ms
Inverter⇔Bypass Mode Inverter Mode or UPS Mode by Switch (Option)
AC Output AC Voltage Adjustment   A: 1Phase 2W+G, 100 - 120 Vac (Tune VR)   E: 1Phase 2W+G, 200 - 240 Vac (Tune VR)
Voltage Accuracy < 2% at Linear Load
Frequency 50Hz / 60Hz ± 0.05% (Switch Selectable)
Output Wave Form Pure Sine Wave, <3% THD @ Resistive Load
Output Power Factor 1.0 1.0
Peak Output Current 54A 27A
Efficiency @ Full Load   86%  88%  89%  94%  94%  87%  90%  92%  94%  94%
No Load Current  Draw 1.50A 0.82A 0.39A 0.16A 0.11A 2.20A 1.08A 0.55A 0.28A 0.12A
Protection Protection    Overload, Short Circuit, Reverse Polarity (Fuse), Input Under Voltage,
Input Over Voltage, Over Temperature 
Safety  EN60950-1
EMC FCC class A 

EN55022: 2006, Class A

EN61000-3 -2: 2006

EN 61000-3-3: 1995+A1:2001+A2-2005

Indicator Digital Display OVP, UVP, OTP, OLP, VAC, AMP, WATT, VDC, TEMP, Hz
Communication Interface Control Unit 

RS-232C with Baud Rate 2400, 4800, 9600, 19200 (Switch Selectable)

Option-1: SNMP Interface

Option-2: Dry Contact: OVP, UVP, OTP, OLP 
Remote Control Unit Optional Can't Support Optional Can't Support
Environment Operating Temperature -20°C ~ 50°C 
Storage Temp. Range -30°C ~ 70°C 
Relative Humidity 0~90%, non-condensing
Cooling Air Forced Fan Loading & Temperature Controlled Cooling Fan
Mechanical Dimension W424 * D435 * H88mm
Net Weight 12.8kgs

* All specifications mentioned above are subject to change without prior notice.

CUSTOMIZATIONS

► HOT STANDBY

► SNMP Interface

► Dry Contacts

► Remote Control

Introduction

12 / 24 / 48Vdc Telecom Inverter, Rack-mount Type is designed for long “MTBF” and continue to provide manageable and dependable AC power for network demands. Featuring an integrated utility bypass function, pure sine wave output and low EMI / RFI emissions, SPI-R series Telecom Inverters are well equipped for Telecom and other demanding critical applications.

An intelligent microprocessor-based control and smart software for power management include alerts on the LED display interface that ensure safety and reliability.
A SNMP option is available; and would allow the user remote communication access to the inverter. SPI-R Series Power Inverters are among the most reliable systems available for electricity and other demanding critical applications.