True Galvanic Isolated On-line UPS (400KVA)
Add in inquiry DownloadType:
IGBT / PWM Type
Capacity:
- Three Phase : 400KVA
Made in:
Taiwan, ROC
Add in inquiry DownloadType:
IGBT / PWM Type
Capacity:
- Three Phase : 400KVA
Made in:
Taiwan, ROC
• AC Power from vehicle battery
• Communications Systems
• Cellular Sites
• Network & Data Center
• Emergency Lighting
• Medical Systems / Hospitals
• Oil & Gas
• Precise Measuring & Testing Equipment
• Transportation Signaling Power
• High Tech Industry
• TV & Radio Broadcasting Stations
• Utility Applications
• MILITARY APPLICATIONS:
• ⇒ Military Program, Aircraft,
• ⇒ Shipboard, Submarine,
• ⇒ Mobile Power Units, Shelters
• ⇒ Military System Diagnostics
• ⇒ Military Research & Defense Weapons
USA Military Approved Power System !
► USA MILITARY APPROVED
► Quality guarantee!
► HIGH EFFICIENCY, OPTIMUM STABILITY, SUPERIOR HEAT DISSIPATION
By use of advanced Technology DPS, IGBT and Switching Components to increase the reliability, efficiency and heat dissipation.
► BUILT-IN AVR FOR WIDER INPUT VOLTAGE RANGE
Input Voltage Range: +/-20% (> +/-20% is available upon request). (AC300V ~ AC520V at 380V Grid, full load mode). Works effectively under any unstable AC source. All of the input components used are specially selected to handle extreme high voltage and high current.
► ZERO INRUSH CURRENT
Current Limit Circuit restricts inrush current so oversize cable and wiring is not required.
► RELIABLE INPUT PROTECTION
Circuit breakers are placed in each individual input loop to ensure power can continue through another loop in case of breaker trip caused by an abnormal condition in either rectifier or load.
► PROTECTION AGAINST DETACHING AND FLOATING OF THE NEUTRAL OF INPUT POWER SUPPLY
An MOV (surge protector) is added at the input, providing protection to both UPS and the load from any lightning surges, or surges caused by neighboring large loads.
► EMI SUPPRESSION
An EMI filter is added to meet the international EMC limits. Therefore, very low noise is emitted, and no interference is supplied to other equipment connected to the same AC source.
► COMPLETE INPUT TO OUTPUT TRUE GALVANIC ISOLATION DESIGN
Solve ultimately power problems, including noise, lightning, ground leakage current, and CEMF (Counter-electromotive Force) etc.
► PROTECTION AGAINST MISUSE
Friendly design. The UPS is designed with breaker on/off sensor, power supply sensor, etc. Therefore, any operational mistake made by the user causes no harm to the UPS.
► COLD START FUNCTION
Can be started without AC source (with battery only). This is possible because current limit circuitry is added, preventing the problem of large inrush current blowing the battery fuse and damaging the DC capacitors when batteries are connected to an empty DC bus (before the DC bus is energized).
► MULTI-CPU DESIGN AND SOFTWARE / HARDWARE COOPERATE CONTROL
Make the system extremely high reliable.
► DIAGNOSTIC PANEL WITH LCD AND LED DISPLAY
1. Local / Remote System Status available 24/7/365.
1. Diagnostic Panel with :
1. • LCD Display real time states, data or historical events, parameters, real time clock, inverter & alarm;
1. • 24 LEDs representing all of the important information of the user. When abnormal conditions occur, these LEDs will light to warn the user of the cause of the faulty condition , events categorized to alarms and notices
2. Multifunctional Control and Readout
► SELF DIAGNOSE, PLUG & PLAY MODULAR DESIGN PCB WITH COLOR MANAGEMENT INDICATORS
All PCBs are Modular design and integrate inside the PCB Holder. In case the SPF series were failed, open the holder, visual inspect the indicator color with beneath descriptions for easy service and quick maintenance.
► PLUG & PLAY MODULAR DESIGN FOR QUICK MAINTENANCE AND TROUBLESHOOTING
The power circuit is separated into several modules plugged into several slots in the unit, which are easy to pull out, permitting quick maintenance and easier troubleshooting (MTTR < 25minutes).
► USER FRIENDLY CONTROL DESIGN
The UPS is designed with breaker on / off sensor, power supply sensor etc. Any operational mistake made by the user causes no harm to the UPS
► RUGGEDNESS
The Rectifier employs phase control technology to regulate the DC bus Voltage. This is the most efficient method to charge the batteries.
The SCR used are inherently rugged. Additionally, a large inductor is added at the input to avoid deforming the AC source waveform.
► Customizations Welcome
Please contact us, we will welcome the opportunity to review your problems and provide you with necessary solutions.
► TOLERATE HARSH ENVIRONMENT
Each component is chosen with large safety margin to accommodate Extreme environments, such as temperature, humidity, altitude, shock or Contamination.
► PHASE CONTROL TECHNOLOGY VIA SCR
1. Most rugged design under poor conditions
2. Most efficient method to charge the battery
3. Inductor added at input to avoid fluctuation
► EACH PHASE WITH INDIVIDUAL INVERTER SUPPORTING
Characteristics will not be violated under 100% unbalance load.
► 300% TRANSIENT OVER CURRENT CAPABILITY
► ALARM FOR OVER VOLTAGE, OVER CURRENT, OVER TEMPERATURE, OUTPUT SHORT CIRCUIT PROTECTION
► INTELLIGENT CHARGER WITH TEMPERATURE COMPENSATION
Prolong the battery life expectancy. And with huge charging Power (selectable), can charge very big capacity, long back-up time battery bank.
► INTELLIGENT, SAFE BATTERY TEST CIRCUITRY
Test the battery without the risk of output AC failure in case of battery bad. And with battery fluid leakage and improper grounding detect circuitry, can ensure safety of the battery bank.
► HUGE CHARGING POWER
The charging power is selectable (Lo/Me/Hi) according to Ah rating of the batteries, and can charge up battery banks providing more than 8Hrs back-up time without adding an extra charger.
► INTELLIGENT FAN SPEED CONTROL
The fan rotation rate can automatically change according to the load condition, so that the fan’s life expectancy is extended and audible noise is reduced.
► REASONABLE HEAT EVACUATION PASSAGE DESIGN
Control circuitry and power circuitry are physically separated. Therefore, the UPS system can operate under harsh environment.
► BASE WITH ANCHOR BOLT FIXING
The floor loading capacity should be high enough to endure the weight of the SPF series. The SPF series is mounted on four right-angled steel angles. Insert corresponding bolts and nut 2 (dia.1/2”) into the floor for securing the SPF series on the floor when it is located in an area where earthquakes is possible, or where motion may occur, e.g. vehicle mounted.
3 PHASE INPUT / 3 PHASE OUTPUT (400KVA)
MODEL |
SPU-33400 |
|||||||
Capacity | 400 KVA | |||||||
INPUT (RECTIFIER) |
||||||||
Input Voltatge (Select One) |
3 Phase 3 Wire+G (Δ): 200/220/380/440/460V (Option:480VΔ / 600VΔ) 3 Phase N+G (Y): 200/208/380/400/415/440V (Option:480VY / 600VY) |
|||||||
Input Voltage Range | ± 20% (> ±20% is available upon request) | |||||||
Input Frequency | 50Hz or 60Hz ± 7Hz (400Hz Option) | |||||||
Power Walk In | 15% ~ 100% : 15 Sec. | |||||||
Efficiency | ≈ 99% | |||||||
BATTERY |
||||||||
Battery Type / pieces | Maintenance Free Lead-acid Batteries / 12V x 29pcs | |||||||
Max. Charge Current Adc (Selectable) | 200 A | |||||||
Battery Start | Yes, UPS can be started without AC Source | |||||||
INVERTER |
||||||||
Output Voltage (Select One) |
3 Phase 3Wire+G (Δ): 200/220/380/440/460V (Option:480VΔ / 600VΔ) 3 Phase N+G (Y): 200/208/380/400/415/440V (Option:480VY / 600VY) |
|||||||
Voltage Regulation Rate | ± 1% | |||||||
Output Wave Form | Pure Sine Wave | |||||||
Output Power Factor | 0.8 | |||||||
Frequency Lock Range | 45 ~ 55Hz / 55Hz ~ 66Hz (400Hz Option) (Select One) | |||||||
Frequency Stability | ±0.1Hz (Crystal Controlled, Free Running) | |||||||
Phase Shift | 120∘±0.5∘(100% Unbalance Load) | |||||||
Total Harmonic Distortion | < 3% (0~100% Linear Load) | |||||||
Overload | < 100% | Continuous | ||||||
110 ~ 124% | 15 Minutes | |||||||
125 ~ 149% | 5 Minutes | |||||||
>/= 150% | 30 Seconds | |||||||
Efficiency (100% Load) | 96 % | |||||||
STATIC SWITCH |
||||||||
Voltage Range | 173 ~ 277 VAC (L-N) (Different voltages are available upon request.) | |||||||
Mains ⇔ Inverter | 0 ms (True Online) Zero cross transfer | |||||||
OVERALL CHARACTERISTICS |
||||||||
Capacity | 400 KVA | |||||||
Overall Efficiency | 94 % | |||||||
Max. Heat Dissipation | 21.7 KW | |||||||
Size (W*D*H / mm) | 2240*1000*1900 mm | |||||||
Weight (KG, W/O Battery) at I/O 380/220V | 3200 kgs | |||||||
Audible Noise | < 72 dBA at 1 meter | |||||||
Relative Humidity | 0%~90% (Non-Condensing) | |||||||
Temperature | 0~40℃(32~104℉) | |||||||
Altitude | <1500M Above Sea Level | |||||||
Protection | Over / Under Voltage, Output Short Circuit, Overload, Over Temperature Protection | |||||||
Lightning / EMC Filter | MOV / Input & Output (FCC CLASS A) | |||||||
Galvanic Isolation | Input and Output True Galvanic Isolation | |||||||
Diagnostic Panel | LCD Display Real Time Status, Historical Events, 24 Status LED Indicators & Alarm | |||||||
Remote Control |
Remote Monitoring 1~99 units simultaneously, distance up to 1,000m |
|||||||
Communication Interface | Dry contact, RS232, RS485 (Optional MobBus protocol or SNMP Card) | |||||||
STANDARDS |
||||||||
EMI / EMC | EN50091-1,-2, CE Approved | |||||||
UL (Option) | ANS/UL1778, 4th Edition, Rev.July 28’06, CAN/CSA C22.2 #107.3-05.Rev.July’06 |
* Remarks:
1. Different specifications required are available
2. All specifications mentioned above are subject to change without prior notice.
CUSTOMIZATIONS
► Single and Three Phase Configurations
► 400Hz Input and / or Output Frequency
► Variable Input & Output Power Configurations (60Hz, 50Hz, 400Hz)
► Inline Voltage and Frequency Converters
► 12-PULSE FULL CONTROLLED RECTIFIER
Reduce harmonic current for 80KVA and above SPM series.
► INPUT HARMONIC FILTER
Reduce T.H.D. (Total Harmonic Distortion) of input current.
► SERIAL & PARALLEL REDUNDANT
A supplemental power supply is added to provide redundancy for supplying power to the static switch, so that there will be AC output no matter what happens to the UPS.
► EMERGENCY STOP SWITCH (EPO)
In case of hazard, for example electric shock, fire or earthquake, the UPS can be shutdown (will have no AC at the output) either through a switch (can be added upon request) or through smoke detector signal (can be added upon request) to prevent further injuries or destruction.
► SHOCK MOUNT
The cabinet can be shock mounted using optional rubber or coil type isolators.
This will enable the unit to withstand shock levels as specified in MIL-S-901.
► CASTERS & LEVELERS
For portability, the cabinets may be optionally equipped with the base-mounted casters / leveler set as shown.
► CABLE ENTRANCE DIRECTION
Cable entry can be from Front, Side, Rear or Top side.
COMMUNICATIONS OPTIONS
► UPSCANTM - Remote Control Panel
A hand held remote display and control module with LCD and LED display that can monitor up to 99 Frequency Converters via RS-485 at a remote distance up to <1,000M (up to 3,000feet)
► GPRS MODEM - Auto-dialing Module
In case of abnormal situation, it will automatically dial to specified service center for help. Multiple phone numbers can be set and no dedicated line is required.
► UPSCOMTM - 3 Phase PC Monitoring Software
Can provide real-time three phases information of Frequency Converter connected on the line and monitor 31 Frequency Converters max. with one PC.
► 3 Phase SNMP Card
Can monitor and manage the Frequency Converters through Web browser and Java applet, providing simultaneously three phases data acquisition.
► DCMANTM - Battery Monitoring Module
An intelligent module to keep watching each battery in a battery bank connected in series and can distinguish and repair the aged battery before it is seriously worn out.
What is "True Galvanic Isolation"?
Usually, Y-caps are installed in UPS’s input & output to eliminate the electro-magnetic interference, but Y-caps will increase the ground leakage current. Together, with the parasitic capacitance of the unit itself the impedance between power lines and ground becomes very low. Therefore, the grounding quality will be affected, resulting in voltage differences between different systems, and problems will arise, such as the connection terminal sparks when plug in the communication port, or the data transmission seriously interfered. The whole LAN system will be contaminated or even computers (equipments) will be destroyed.
The best way to prevent and solve this problem is to completely isolate the UPS output from the input power system. In that case, the UPS output can be tied to any ground at any potential. Not only the noise inside the UPS is stopped, and the output neutral can adapt to any voltage induced by complicated connection of the load system, but also can stop the electro-magnetic interference, surge, and spikes caused by lightning or heavy / inductive load impact / detach nearby, comes through the UPS to the load. Beside, output can remain safe even when neutral is disconnected. Now, protections against over-shoot voltage are explained below.
Comparative System Diagram
Fig 1: SPU True Galvanic Isolated UPS
Fig 2: Non-true Galvanic Isolation